- cooling and dehumidification- switch on the compressor of the refrigeration system. Cool the air until 18°C to 20°C (stable temperature), and then print the data and chart. Calculate the heat rate amount of moisture removed from the air.
Schematic diagram psychrometric chart
Cooling and Dehumidification w1= w2
Tdry = 31.1 Tdry = 19.9
Twet = 25.8 Twet = 18.9
From Psychrometric Chart
ω1 = 0.01925 kg/kga 3= 0.01336 kg/kga
Ø1= 66% Ø3= 92%
h1 = 80 h2= 74 h3 = 54
Qout = ma( h1- h2) + mfhf
mv2 = ω2 ma = 0.01925( 91.7x 10-3) = 1.765 x 10-3
mv3 = ω3 ma = 0.01336( 91.7x 10-3)= 1.225 x 10-3
mf = mv2 – mv1
= (1.765 – 1.225) x 10-3
= 5.4 x 10 -4
hf = h2- h3 = 74 – 54 = 20 kJ/kg
☼ Qout = 91.7x 10-3( 80 – 74) + (5.4 x 10 -4 )(20)
= 0.561 kJ